Maidencreek Township Authority
Water System Identification - PWSID 3060012

Consumer Confidence Report – 2014

ESTE INFORME CONTIENE INFORMACIÓN MUY IMPORTANTE SOBRE SU AGUA POTABLE.
TRADÚZCALO O HABLE CON ALGUIEN QUE LO ENTIENDA BIEN.

In accordance with the Environmental Protection Agency’s reporting requirements, we are pleased to provide you with this year's Consumer
Confidence Report for the Maidencreek Township Authority. We want to keep you informed about the excellent water and services we have
delivered to you over the past year. Our goal is, and always has been, to provide to you a dependable supply of drinking water. Our water
source is groundwater wells. The primary water sources are Well #3 located along Wesner Road, Well # 5 located along Burgert Lane, and
Well #2 located on June Avenue. All of our sources are located within Maidencreek Township. We’re pleased to report that our
drinking water meets federal and state requirements.

If you have any questions or comments about this report or concerning your water utility, please contact Mr. Patrick Donovan at 610-926-
4173. We want our valued customers to be informed about their water utility. If you want to learn more, please attend any of our regularly
scheduled meetings. Meetings are held on the second Wednesday of every month at the Maidencreek Township Building located at One
Quarry Road, Blandon.

The Maidencreek Township Authority routinely monitors for constituents in your drinking water according to Federal and State laws. The
table contained within this report shows the results of our monitoring for the period of January 1st to December 31st, 2014. All drinking
water, including bottled drinking water, may be reasonably expected to contain at least small amounts of some constituents. It's important to
remember that the presence of these constituents does not necessarily pose a health risk.

You will find many terms and abbreviations you might not be familiar with contained within the tables of this report. To help you better
understand these terms; we've provided the following definitions:

Non-Detects (ND) - laboratory analysis indicates that the contaminant is not present at a detectable level.

Parts per million (ppm) or Milligrams per liter (mg/l) - one part per million corresponds to one minute in two years or a single penny in
$10,000.

Parts per billion (ppb) or Micrograms per liter - one part per billion corresponds to one minute in 2,000 years, or a single penny in
$10,000,000.

Action Level (AL) –the concentration of a contaminant, which, if exceeded, triggers treatment or other requirements which a water system
must follow.

Treatment Technique (TT) - A treatment technique is a required process intended to reduce the level of a contaminant in drinking water.

Maximum Contaminant Level - The “Maximum Allowed” (MCL) is the highest level of a contaminant that is allowed in drinking water.
MCL’s are set as close to the MCLG’s as feasible using the best available treatment technology.

Maximum Contaminant Level Goal - The “Goal”(MCLG) is the level of a contaminant in drinking water below which there is no known or
expected risk to health. MCLG’s allow for a margin of safety.

Picocuries Per Liter – Measure of radiation. (pCi/L)

Maximum Residual Disinfectant Level (MRDL) - The highest level of a disinfectant allowed in drinking water. There is convincing
evidence that addition of a disinfectant is necessary for control of microbial contaminants.

Maximum Residual Disinfectant Level Goal (MRDLG) - The level of a drinking water disinfectant below which there is no known or
expected risk to health. MRDLGs do not reflect the benefits of the use of disinfectants to control microbial contamination.

TEST RESULTS

Inorganic Contaminants

Contaminant (Unit of Violat Level Range MCLG MCL Likely Source of Contamination
measurement) ion Detected
Y/N 4.4 – 6.3 10 10 Runoff from fertilizer use; leaching
1. Nitrate(as Nitrogen) 6.3
(ppm) N

from septic tanks, sewage; erosion of

natural deposits

2. Barium (ppm) N 0.03410 .0328-.0341 2 2 Discharge of drilling waste; discharge
(2009)
from metal refineries; Erosion of

natural deposits.

3. Nickel (ppm) N .0016 .0007-.0016 .1 .1 Erosion of natural deposits.
4. TCE (ppb) (2009)
5. Fluoride (ppm)
N 0.5 0.0 - .5 0 5.0 Discharge from factories or dry

(2010) cleaners.

N 0.77 0.77 2* 4 Water additive which promotes

(2012) (c) strong teeth.

Microbiological Contaminants

Contaminant (Unit of Violation Level Range MCLG MCL Likely Source of
measurement) Y/N Detected Contamination
No more than 5 % Naturally present in
1. Total Coliform N 0 0 – 5.0 0 positive samples per the environment.

Bacteria % month.

(positive/negative)

Lead and Copper Contaminants

Contaminant (Unit Violation of Level Detected Units MCLG Action # of Sites Likely Source of
of measurement) TT 90 th Percentile Level Above AL of Contamination
Y/N (AL) Total Sites
Value

1. Lead (ppb) N 5.0 ppb 0 15 1 out of 20 Corrosion of household

(2013) (a) plumbing.

2. Copper (ppm) N 0.167 ppm 1.3 1.3 0 out of 20 Corrosion of household
(2013)
(b) plumbing.

Footnotes:

(a) 19 of 20 samples were less than the Action Level.

(b) 20 of 20 samples were less than the Action Level.

(c) EPA’s MCL for fluoride is 4 ppm. However, our state has set a lower MCL to better protect Human health.

Radioactive Contaminants

Contaminant (Unit of Violation Level Range MCLG MCL Likely Source of Contamination
measurement) Y/N Detected N/A 15 Erosion of Natural Deposits.
5.0 N/A
1. Gross Alpha/Exc N 5.0 0-1.35 N/A
Radon & Uranium 1.43
(pCi/l) N 1.35 5 Erosion of Natural Deposits.

2. Radium 228 (pCi/l) (2008)

3. Radium 226 (pCi/l N 1.43 5 Erosion of Natural Deposits

(2011)

Disinfection Byproducts, Byproduct Precursors, and Disinfectant Residuals

Contaminant (Unit of Violation Level Range MCLG MCL Likely Source of Contamination

measurement) Y/N Detected

1. TTHMs (Total N 24.1 24.1 N/A 80 Byproduct of drinking water

trihalomethanes) chlorination

(ppb)

2. Haloacetic Acids N 1.7 1.7 N/A 60 Byproduct of drinking water
(ppb)
chlorination
3. Chlorine (ppm)
N 1.32 0 - 1.32 MRDLG - 4 MRDL - 4 Water additive used to control

microbes.

Distribution Disinfectant Residuals

Contaminant (Unit of measurement) Minimum Highest Range of Month w/ Viola Likely Source of
Disinfectant Average Monthly Avg Highest Avg tion Contamination
Result Y/N
Residual Results Results Water Additive used to
No control microbes
1. Chorine (ppm) 0.73 0.92 0.73- .92 Nov

The Authority adds fluoride to its water supply for health benefits. The primary health benefit is the prevention of tooth decay. Fluoride is
applied at a dosage rate of 0.75 part per million. The State determined this dosage rate to be the best for our climate. The American Dental
Association (ADA) issued interim guidance on fluoride intake for infants and young children in November of 2006. You can log onto the
ADA website for additional information. You can also find information on the Center for Disease Control website at
http://www.cdc.gov/fluoridation/safety/infant_formula.htm. If you have questions regarding the optimum dosage rates for your family
members you should speak with your dentist or pediatrician. Individuals with medical conditions that require them to limit their intake of
fluoride are advised to consult with their physicians.

In January 2014 we did not report the monthly chlorine residuals to PA DEP until January 17, 2014, seven days past the required reporting
deadline. This occurred due to miscommunication between the general manager and operations staff. Corrective actions have been taken.
The operations staff started reporting to the state earlier in the month, and chlorine data will be submitted no later than the 10th of each month.

The State allows us to monitor for some contaminants less than once per year because the concentrations of these contaminants do not change
frequently. Some of our data, though representative, are more than one year old. Data on Barium, Nickel, TCE, Fluoride, Lead, Copper,
Radium 226, and Radium 228, are more than one year old. The date, which corresponds with the data presented in the table, is located below
the detected levels. What does this mean? As you can see by the table, our system had no violations. We’re proud that your drinking water
meets or exceeds all Federal and State requirements. We have learned through our monitoring and testing that some constituents have been
detected. In addition to the Contaminants listed in the chart above, the Maidencreek Township Authority routinely tests for bacteria.

Certain minerals are radioactive and may emit a form of radiation known as alpha radiation. Some people who drink water containing alpha
emitters in excess of the MCL over many years may have an increased risk of getting cancer. Some people who drink water containing
radium 226 or 228 in excess of the MCL over many years may have an increased risk of getting cancer.

All sources of drinking water are subject to potential contamination by constituents that are naturally occurring or man made. Those
constituents can be microbes, organic or inorganic chemicals, or radioactive materials. All drinking water, including bottled water, may
reasonably be expected to contain at least small amounts of some contaminants. The presence of contaminants does not necessarily indicate

that the water poses a health risk. More information about contaminants and potential health effects can be obtained by calling the
Environmental Protection Agency’s Safe Drinking Water Hotline at 1-800-426-4791.

A Source Water Assessment of the Authority’s groundwater wells which serve as our community water supply was completed in 2003 by the
PA Department of Environmental Protection (PA DEP). The Assessment has found that are groundwater supplies are most susceptible to
transportation corridors (roads and railways), mulching and composting facilities, and industrial discharges. Overall, our water supply has a
moderate risk of significant contamination. Final reports will be available at the Maidencreek Township Authority office when final copies
are received from PA DEP.

MCL’s are set at very stringent levels for health effects. To understand the possible health effects described for many regulated constituents, a
person would have to drink 2 liters of water every day at the MCL level for a lifetime to have a one-in-a-million chance of having the
described health effect.

Some people may be more vulnerable to contaminants in drinking water than the general population. Immuno-compromised persons such as
persons with cancer undergoing chemotherapy, persons who have undergone organ transplants, people with HIV/AIDS or other immune
system disorders, some elderly, and infants can be particularly at risk from infections. These people should seek advice about drinking water
from their health care providers. EPA/CDC guidelines on appropriate means to lessen the risk of infection by cryptosporidium and other
microbiological contaminants are available from the Safe Drinking Water Hotline (800-426-4791).

If present, elevated levels of lead can cause serious health problems, especially for pregnant women and young children. Lead in drinking
water is primarily from materials and components associated with service lines and home plumbing. Maidencreek Township Authority is
responsible for providing high quality drinking water, but cannot control the variety of materials used in plumbing components. When your
water has been sitting for several hours, you can minimize the potential for lead exposure by flushing your tap for 30 seconds to 2 minutes
before using the water for drinking or cooking. If you are concerned about lead in your water, you may wish to have your water tested.
Information on lead in drinking water, testing methods, and steps you can take to minimize exposure is available from the Safe Drinking
Water Hotline or at http://www.epa.gov/safewater/lead.

Please call our office if you have questions. We at Maidencreek Township Authority work around the clock to provide top quality water to
every tap. We ask that all our customers help us protect our water sources, which are the heart of our community, our way of life and our
children’s future.