MAIDENCREEKTWP.PLANNING COMMISSION
P.O.BOX 319, BLANDON, PA 19510
January 7, 2016
Maidencreek Township Board of Supervisors
POBox319
Blandon, PA 19510
Dear Sirs,
At their January 6, 2016 meeting, the Maidencreek Township Planning Commission
recommended that the Board of Supervisors grant a waiver to Chapter 186, Article VII -
Lighting Standards for the Brandywine Transportation Plan. The Commission asks for a
note on the plan that the waiver is for the specific use of the bus terminal. Any change of
use should require a lighting plan be reviewed and approved by the Township. I have
included a copy of the January 5, 2016 review letter for your review.
Sincerely,
haeh
ame
Diane Hollenbach
Manager
Maidencreek Township
cc:
File
John Hoffert Surveying
Hartman, Valeriano, Magovern & Lutz P.C.

John Hoffert
John W.Hoffert, P.L.S., LTD.
JohnW.Hoffert,P.L.S.
Phone: 610-775-0465
32 E.Lancaster Avenue
FAX: 610-775-7815
Surveying
Shillington,PA19607
Email:john@hoffertsurveyors.com
January 6, 2016
Maidencreek Board of Supervisors
Maidencreek Township Planning Commission
P.0. Box 529
Blandon, PA 19510
Re: Brandywine Transportation Lighting
Waiver Request
Dear Township Officials:
We are hereby requesting a waiver of Chapter 186, Article VII -Lighting Standards on
the condition that the Applicant installs the lighting in accordance with a revised lighting
plan acceptable to the Township and the Applicant.
Thank you for your consideration of this request.
Sincerely
John W. Hoffert, P.L.S.

Lighting Plan for Bill Gross
https://mail.aol.com/webmail-std/en-us/PrintMessage
From:ElizabethMagovern<emagovern@hvmllaw.com>
To: Diane Hollenbach (maidentwp@aol.com)<maidentwp@aol.com>
Cc: William Gross <bill.e.g@hotmail.com>
Subject:Lighting Plan forBill Gross
Date: Wed, Dec 23, 2015 12:29 pm
Diane,
Ray Martin dropped off the revised lighting plan to you this morning. On the second page of the plan, the
highlighted portions in pink represent the areas where Mr. Gross would like to place the LED lights. The blue
highlighted portions on the plan represent the original lighting that was required in the original plan. Also,
please be advised that the building also has exterior lights on it in addition to the lights being proposed. We also
will not require that. There is no lighting along West Wesner Road and therefore, we do not feel it is necessary
to place lights along the driveway especially in light of the neighbors' concerns about lighting. Let me know if
you need us to do anything else. We can come to a Bos meeting if needed. Have a wonderful holiday!
Liz Magovern
Elizabeth A. Magovern, Esquire
Hartman, Valeriano, Magovern & Lutz, P.C
1100 Berkshire Blvd., Ste. 301
P.0.Box 5828
Wyomissing, PA 19610
(610) 779-0772
amel
1 of 1
12/23/20151:18PM

PHONE:(610)375-8822
GREATVALLEY CONSULTANTS
1-800-733-4821
FAX: (610) 375-8977
75COMMERCEDR/VEWYOMISSING,PA19610-3323
January 5, 2016
Maidencreek Township
Planning Commission
P. O. Box 319
Blandon,PA19510
Attention;
Diane Hollenbach, Township Manager
Re:
Brandywine Transportation
Lighting PlanReview
GVC File 4026-001
DearPlanning Commissioners:
We received for review highlighted plans titled "Brandywine Transportation," submitted by Ray
Martin. The plans indicate approved lighting fixtures in blue and proposed lighting fixtures in
pink.
Please note comments in bold typeface require action by or consideration of the Planning
Commission and Board of Supervisors. The remaining comments should be addressed by the
Applicant or his consultant, directly with Township staff or our office. The plan was reviewed
for conformity with Township Ordinances and Standards, as well as accepted engineering
practice. We offer the following comments for your consideration:
SUBMISSIONINFORMATION
1.
Highlighted plans titled “"Brandywine Transportation", prepared by John W. Hoffert,
PLS, and Applied Surveying Technologies, Inc., consisting of two plan sheets as listed:
Date
Sht. No.
Plan No.
Description
Originated
Revised
D-15-16-ES3
1/21/15
5/19/15
PCSM Plan East
7 of 12
1/21/15
5/19/15
5410-11-56-9323-D-007
Grading & Utility Plan (West)
LIGHTING PLANS
1.
The proposed revised plan does not indicate if the fixtures and poles are to be the same
type as indicated in the approved Land Development Plan. This information should be
provided. If the fixtures are to be different than previously approved, we will need the
catalog cuts of the fixtures noting the type of light, wattage, lumen output and
photometrics of the fixture.
2.
The plan does not indicate the footcandle levels of the revised arrangement. This
information is necessary to confirm compliance with $186-47 of the Township's Codified
Ordinances.
Engineers → Architects → Pianners → Consultants → Surveyors
printed on recycled paper

GREATVALLEY CONSULTANTS
Maidencreek Township
January 5, 2016
Planning Commission
It is our impression that the proposed revised layout will not provide the required 1.0
average footcandle level on the parking areas, but this needs to be verified with the
submission of the footcandle plan. The plan would also need to demonstrate that the
revisions would comply with the Uniformity Ratio of 3:1.
The plan should also include the footcandle levels of any light fixtures attached to the
building, along with the type of light, wattage, lumen output and photometrics of the
fixtures. The plan should demonstrate that the light level at the main entrance to the
building complies with the required 5.0 average footcandle level.
3.
The approved Land Development Plan indicates site lighting fixtures along the access
drive to the site from West Wesner Road. The applicant has requested that these fixtures
be deleted since there is no existing street lighting on the section of West Wesner Road in
the vicinity of the intersection of this access drive. The reason for this request is to
address concerns by the neighbors that the lighting of this drive might impose glare or
otherwise disturb the neighborhood.
We note that s186-47 does not specifically address requirements for lighting on
access drives to commercial parking areas. It is our recommendation that this
request be discussed by the Planning Commission. Since there is no pedestrian
traffic expected on this access drive, it is our opinion that deletion of the fixtures
from the access drive would not be a safety concern.
PREVIOUS OUTSTANDING REVIEW COMMENTS
Additional comments may result from any revisions to the plans currently under review.
Please do not hesitate to call our office with any questions regarding the above review.
Sincerely,
CHARLES M. JONES,PE, PLS
Project Manager
CMJ:lam
cC:
Maidencreek Township Board of Supervisors
Eugene Orlando, Esquire
Elizabeth A. Magovern, Esquire
Terry Naugle, GVC