MEMO
To:
MaidencreekBOS
From: Thomas S.Unger, P.E.
Date:4/11/18
On MondayApril 3, 2018 SDEl performed a walk through evaluationof the Maidencreek
Township Municipal Building's HVAC system.The purpose of the evaluation was to determine if
there was a simple solution to remedy a problem with fumes from the facility's service garage
areamigratingtothefacility'sofficespaces.
Per our walk through,it appears the office portion of thefacilityoperated at a negative
pressure with respect to the garage area. This differential pressure forces fumes to migrate
fromthegarageareatotheofficespace.
The existing HVAC system for the office space utilize horizontal gas fired furnaces with add on
split system air conditioning.The systems arefully ducted but not sealed for low leakage.There
is no outside air introduced into the systems as the code required ventilation appears to be
provided by natural means through operable windows.
The existing HVAC system for the garage is horizontal gas fired unit heaters. There is no outside
air introduced into the garage, as there are operable overhead doors.No localized exhaust
systems existwithinthegarage.
Beforeanything isdone withthe HVACsystem it is recommended steps betaken to tighten the
boundary between the spaces. By sealing the partition that forms the boundary and reducing
the open space or air gaps, the fume transport airflow can effectively be reduced.
Once the boundary is made as tight as possible, the fume issue can be further remedied by
reversing the pressure relationship between the office space and the garage.The office space
accomplished by either increasing the office pressure or decreasing the garage pressure.
To increase the office pressure the Township would have to introduce ventilation or outside air
through the HVAC equipment. However due to the amount of air that would be required this
cannot be done with the existing equipment as it would not have adequate heating and cooling
capacity. This would require replacing the existing office HVAC entirely; which would likely cost
in the six figure range.
To decrease the pressure within thegarage space exhaust fans could be added to capture the
fumes at their source and expel them outside of the building.These fans could be operated
intermittently when fume generating work is being performed. However, during operations in
winter months the additional exhaust will draw unconditioned air into the building.This
unconditioned air will require additional heat be added to the garage area. While adding

exhaust will be less expensive than replacing the office HVAC it will still have a significant price
tag.It will likelycost30-75%ofwhat replacingtheofficeHVACwill cost.
At this time, should you choose to take action, we recommend moving forward with sealing the
boundary wall.Once this is done thefacility can be operated as normal and somefurther
evaluationscanbemade.